1SDA067037R1
Description
Achieve ultimate flexibility and robust fault protection with the ABB SACE Tmax XT2N 160. This 4-pole Molded Case Circuit Breaker (MCCB) features an adjustable thermomagnetic release (TMA) rated at 63A, allowing you to precisely calibrate your overload protection while fine-tuning the magnetic trip to match your specific load requirements.
Unlike standard breakers, this unit offers an adjustable instantaneous short-circuit setting (300A - 630A), allowing you to prevent nuisance tripping from motor inrush currents while maintaining high safety standards.
Built on the robust XT2N frame, this breaker provides a reliable breaking capacity for standard commercial and light industrial power distribution systems. It offers excellent versatility with a rated operational voltage of up to 690V AC and 500V DC, making it an ideal choice for protecting control circuits, small transformers, and sensitive sub-distribution panels.
Engineered for longevity, it delivers a mechanical lifespan of 25,000 cycles and an electrical lifespan of 8,000 cycles. With front bolt terminals designed for busbars ranging from 32.5 to 100 mm², installation is secure, straightforward, and space-efficient. The 4-pole configuration ensures full neutral protection.
Specifications
| Poles | 4P |
|---|---|
| Rated current | 63A |